DEM4A Series Single Phase Power Meter
LCD Display layout
Different values with different indicators
Description
DEM4A009 |
DEM4A00B/10B |
A Impulse indication for active energy B Impulse indication for reactive energy C Far IR D Button for data checking E Button for data setting F SO1 output for active energy (default) G SO2 output for reactive energy (default) H LCD screen |
I Impulse indication for active energy J Impulse indication for reactive energy K Far IR L Button for data checking M Button for data setting N SO1 output for active energy (default) O SO2 output for reactive energy (default) P RS485 output Q LCD screen |
DEM4A20B/30B |
A LCD screen B Impulse indication for active energy C Impulse indication for reactive energy D SO output E Optical port F External Signal input G Left Button for data checking H RS485 output I Right button for data checking and data setting |
Meter Dimensions
Wiring Connection
DEM4A009
Note: 15 16:SO1 is SO output for kWh or Active/reactive forward kWh optional
17 18:SO2 is SO output for kvarh or Active/reactive reverse kWh optional
DEM4A00B/10B
Note:
15 16:SO1 is SO output for kWh or Active/reactive forward kWh optional
17 18:SO2 is SO output for kvarh or Active/reactive reverse kWh optional
19 20:RS485 output
DEM4A20B/30B
Note:
15 16: SO is SO output for kWh
17 18: for external signal input ,important notice :no high voltage input !
19 20: RS485 output
Content |
Parameters |
Standard |
EN50470-1/3 |
Rated Voltage |
3*230(400)V |
Rated Current |
0,25-5(30)A,0,25-5(32)A,0,25-5(40)A,0,25-5(45)A, 0,25-5(50)A,0,25-5(60)A, 0,5-10(80)A,0,5-10(100)A |
Impulse Constant |
1000imp/kWh(LED) 1000imp/kvarh(LED) |
Frequency |
50Hz |
Accuracy Class |
B |
LCD Display |
LCD 6+2 = 999999.99kWh |
Working Temperature |
-40~70℃ |
Storage Temperature |
-40~70℃ |
Power Consumption |
<12VA <1W |
Average Humidity |
≤75% (Non Condensing) |
Maximum Humidity |
≤95% |
Start Current |
0.004Ib |
Case Protection |
IP51 indoor |
Type |
DEM4A009 |
DEM4A00B |
DEM4A10B |
DEM4A20B |
DEM4A30B |
Software Version |
V301 |
V301 |
V301 |
V301 |
V301 |
CRC |
708A |
5B61 |
2B60 |
5B61 |
2B60 |
Impulse Constant |
1000imp/kWh 1000imp/kvarh |
1000imp/kWh 1000imp/kvarh |
1000imp/kWh 1000imp/kvarh |
1000imp/kWh 1000imp/kvarh |
1000imp/kWh 1000imp/kvarh |
Communication |
IR |
IR,RS485 Modbus/DLT645 |
IR,RS485 Modbus/DLT645 |
IR,RS485 Modbus/DLT645 |
IR,RS485 Modbus/DLT645 |
Baud rate |
N/A |
960019200 38400115200 |
960019200 38400115200 |
960019200 38400115200 |
960019200 38400115200 |
SO output |
SO1 is SO output for kWh(default) or Active/reactive forward kWh optional with variable constantDivisible by 96000 | SO1 is SO output for kWh(default) or Active/reactive forward kWh optional with variable constantDivisible by 96000 | SO1 is SO output for kWh(default) or Active/reactive forward kWh optional with variable constantDivisible by 96000 | SO output for Active kWh with variable constantDivisible by 96000 | SO output for Active kWh with variable constantDivisible by 96000 |
SO2 is SO output for kvarh (default) or Active/reactive reverse kWh optionalwith variable constant Divisible by 96000 | SO2 is SO output for kvarh (default) or Active/reactive reverse kWh optionalwith variable constant Divisible by 96000 | SO2 is SO output for kvarh (default) or Active/reactive reverse kWh optionalwith variable constant Divisible by 96000 | Signal input port | Signal input port | |
Pulse width |
Changeable pulse width according to current, the bigger the current the shorter the pulse width |
||||
Backlight |
Blue |
Blue |
Blue |
Blue |
Blue |
Li-Battery |
N/A |
N/A |
YES |
N/A |
YES |
Multi-tariff |
N/A |
N/A |
YES |
N/A |
YES |
Measurement Mode |
1.total =forward 2.Total=reverse 3.Total =forward +reverse (default) 4.Total=Forward-Reverse |
||||
Button |
Touch button |
Touch button |
Touch button |
Touch button |
Touch button |
Button function |
Left button:Page turning, Right button: Page turning,setting information display |
||||
Default setting |
1000imp/kWh 1000imp/kvarh |
1000imp/kWh 1000imp/kvarh 9600/NONE /8/1 |
1000imp/kWh 1000imp/kvarh 9600/NONE /8/1 |
1000imp/kWh 9600/NONE /8/1 |
1000imp/kWh 9600/NONE /8/1 |
Measurement Mode setting |
Button |
RS485 or Button |
RS485 or Button |
RS485 or Button |
RS485 or Button |